🇵🇱 POLITECHNIKA KRAKOWSKA im. Tadeusza Kościuszki PL
ConstructionWater & wastewater
POLITECHNIKA KRAKOWSKA im. Tadeusza Kościuszki is a laboratory accredited by PCA under number AB 1632 (Kraków, Poland). Its accreditation scope covers 34 test methods in the following areas: Construction, Water & wastewater. Test objects include: Ventilation and air conditioning units, Non-metallic ventilation ducts, Terminal ventilation devices Control and shut-off dampers, Air terminal devices Louvre grilles.
At a glance
- Accreditation number: PCA AB 1632
- Methods in scope: 34
- Types of test objects: 19
- City: Kraków, Poland
- Accreditation number
- AB 1632
- Accreditation body
- PCA
- Address
- LABORATORIUM INŻYNIERII CIEPLNEJ, ul. Warszawska 24, 31-155 Kraków
- City
- Kraków, Poland
What this laboratory tests (19)
- Ventilation and air conditioning units — 10 methods
- Non-metallic ventilation ducts — 3 methods
- Terminal ventilation devices Control and shut-off dampers — 3 methods
- Air terminal devices Louvre grilles — 2 methods
- Glazing — 2 methods
- Curtain walling — 1 method
- Frames Dimensions of objects up to 1,50 m x 1,50 m — 1 method
- Roller shutter boxes Dimensions of objects up to 1,50 m x 1,50 m — 1 method
- Roof windows and other windows projecting from the plane Dimensions of items up to 1,50 m x 1,50 m — 1 method
- Sections of window and door frames, their connections with glazing, shutters, shutter boxes — 1 method
- Sheet metal ventilation ducts of circular cross-section — 1 method
- Sheet metal ventilation ducts of rectangular cross-section — 1 method
- Straight ventilation ducts and fittings of circular cross-section — 1 method
- Straight ventilation ducts and fittings of rectangular cross-section — 1 method
- Windows and doors — 1 method
- and 4 more
Accreditation scope — test methods (34)
| No. | Test object | Methodology / Parameters | Technique | Reference document | |
|---|---|---|---|---|---|
| Test methods | |||||
| 1 | Windows, doors, roof windows, windows or rooflights projecting beyond the face of building envelopes | Thermal transmittance Calculation method | PN-EN ISO 10077-1:2017 “N” PN-EN ISO 10077-2:2017- 10/A1:2025-06 “N” | ||
| 2 | Sections of window and door frames, their connections with glazing, shutters, shutter boxes | Thermal transmittance Calculation method | PN-EN ISO 10077-2:2017- 10/A1:2025-06 “N” PN-EN ISO 10211:2017 | ||
| 3 | Curtain walling | Thermal transmittance Calculation method | PN-EN ISO 12631:2017 PN-EN ISO 6946:2017 PN-EN ISO 10211:2017 | ||
| 4 | Glazing | Thermal transmittance Calculation method | PN-EN 673:2025-05 “N” | ||
| 5 | Windows, doors Dimensions of items up to 1,50 m x 1,50 m | Thermal transmittance Hot box method, U range from 0,15 W/(m2k) to 3 W/(m2k) | PN-EN ISO 12567-1:2010+AC:2010 “N” PN-EN ISO 8990:1998 | ||
| 6 | Roof windows and other windows projecting from the plane Dimensions of items up to 1,50 m x 1,50 m | Thermal transmittance Hot box method, U range from 0,15 W/(m2k) to 3 W/(m2k) | PN-EN ISO 12567-2:2006 “N” PN-EN ISO 8990:1998 | ||
| 7 | Frames Dimensions of objects up to 1,50 m x 1,50 m | Thermal transmittance Hot box method, U range from 0,15 W/(m2k) to 3 W/(m2k) | PN-EN 12412-2:2005 PN-EN ISO 8990:1998 | ||
| 8 | Roller shutter boxes Dimensions of objects up to 1,50 m x 1,50 m | Thermal transmittance Hot box method, Range U from 0,15 W/(m2k) to 4 W/(m2k) | PN-EN 12412-2:2005 PN-EN ISO 8990:1998 | ||
| 9 | Terminal ventilation devices Control and shut-off dampers | Tightness of dampers Air flow measurement method Range: from 0,18 m3/h to 1100 m3/h | PN-EN 1751:2024-10 PN-EN 13053:2020 | ||
| 10 | Terminal ventilation devices Control and shut-off dampers | Mechanical testing of control and shut-off dampers Method of measuring the torque on the damper spindle Range: from 0,2 Nm to 20 Nm | PN-EN 1751:2024-10 PN-EN 13053:2020 | ||
| 11 | Terminal ventilation devices Control and shut-off dampers | Aerodynamic characteristics of the damper Air flow measurement method Range: from 1 m3/h to 18000 m3/h | PN-EN 1751:2024-10 PN-EN 13053:2020 | ||
| 12 | Sheet metal ventilation ducts of rectangular cross-section | Duct tightness Air flow rate measurement method Range: from 0,18 m3/h to 1100 m3/h | PN-EN 1507:2007 | ||
| 13 | Sheet metal ventilation ducts of circular cross-section | Duct tightness Air flow rate measurement method Range: from 0,18 m3/h to 1100 m3/h | PN-EN 12237:2005 | ||
| 14 | Non-metallic ventilation ducts | Duct tightness Air flow rate measurement method Range: from 0,18 m3/h to 1100 m3/h | PN-EN 17192:2019 | ||
| 15 | Non-metallic ventilation ducts | Pressure drop Air flow measurement method Range: from 1 m3/h to 18000 m3/h | PN-EN 17192:2019 | ||
| 16 | Windows and doors | Air permeability Air flow measurement method Range: 0,18 m3/h to 1100 m3/h | PN-EN 1026:2016 „N” | ||
| 17 | Windows, doors Dimensions of items up to 2,00 x 2,50 m | Soft and heavy body impact Impact pendulum method with a mass of 50 kg Pendulum drop height range up to 2,0 m | PN-EN 13049:2023 | ||
| 18 | Windows, doors Dimensions of items up to 1,50 x 1,50 m | Watertightness Water penetration test method Water spray rate from 1 l/(min nozzle) to 2 l/(min nozzle) Applied pressure up to 2500 Pa | PN-EN 1027-2016 | ||
| 19 | Ventilation and air conditioning units | Mechanical strength of the enclosure Test pressure range: up to 3000 Pa | PN-EN 1886:2008 | ||
| 20 | Ventilation and air conditioning units | Enclosure tightness Air flow measurement method Air leakage range: from 0,18 m3/h to 1100 m3/h | PN-EN 1886:2008 PN-EN 13053:2020 | ||
| 21 | Ventilation and air conditioning units | Tightness of filter installation Air flow measurement method Air leakage range: from 0,18 m3/h to 1100 m3/h | PN-EN 1886:2008 PN-EN 13053:2020 | ||
| 22 | Ventilation and air conditioning units | Thermal properties of the enclosure Range U from 0,15 W/(m2K) to 6 W/(m2K) | PN-EN 1886:2008 | ||
| 23 | Ventilation and air conditioning units | Sound insulation of the enclosure Noise attenuation range Dp from 5,0 dB to 70,0 dB | PN-EN 1886:2008 | ||
| 24 | Ventilation and air conditioning units | Mechanical safety | PN-EN 1886:2008 | ||
| 25 | Ventilation and air conditioning units | Aerodynamic characteristics of the air handling unit Air flow range of the unit: from 200 m3/h to 18000 m3/h | PN-EN 13053:2020 | ||
| 26 | Ventilation and air conditioning units | Heat recovery section / heat recovery efficiency Air flow range of the section: from 200 m3/h to 3000 m3/h | PN-EN 13053:2020 | ||
| 27 | Ventilation and air conditioning units | Average air velocity in the enclosure Range of the air handling unit air flow: from 200 m3/h to 18000 m3/h | PN-EN 13053:2020 | ||
| 28 | Ventilation and air conditioning units | Fan drive power in the air handling unit Air flow range of the unit: from 200 m3/h to 18000 m3/h | PN-EN 13053:2020 | ||
| 29 | Air terminal devices Louvre grilles | Aerodynamic characteristics of the grille Air flow range: from 200 m3/h to 18000 m3/h | PN-EN 13030:2002 | ||
| 30 | Air terminal devices Louvre grilles | Rainwater penetration Air flow range: from 200 m3/h to 18000 m3/h | PN-EN 13030:2002 | ||
| 31 | Straight ventilation ducts and fittings of rectangular cross-section | Dimensions Dimension range: from 10 mm to 5000 mm | PN-EN 1505:2001 | ||
| 32 | Straight ventilation ducts and fittings of circular cross-section | Dimensions Dimension range: from 10 mm to 5000 mm | PN-EN 1506:2007 | ||
| 33 | Glazing | Light and solar properties Calculation method | PN-EN 410:2011 „N” | ||
| 34 | Non-metallic ventilation ducts | Thermal resistance Calculation method | Procedura Badawcza PB 12 wydanie 1 z 13.01.2023 r. | ||
Reference standards (22)
PN-EN 1026:2016 „N”
PN-EN 1027-2016
PN-EN 12237:2005
PN-EN 12412-2:2005 PN-EN ISO 8990:1998
PN-EN 13030:2002
PN-EN 13049:2023
PN-EN 13053:2020
PN-EN 1505:2001
PN-EN 1506:2007
PN-EN 1507:2007
PN-EN 17192:2019
PN-EN 1751:2024-10 PN-EN 13053:2020
PN-EN 1886:2008
PN-EN 1886:2008 PN-EN 13053:2020
PN-EN 410:2011 „N”
PN-EN 673:2025-05 “N”
PN-EN ISO 10077-1:2017 “N” PN-EN ISO 10077-2:2017- 10/A1:2025-06 “N”
PN-EN ISO 10077-2:2017- 10/A1:2025-06 “N” PN-EN ISO 10211:2017
PN-EN ISO 12567-1:2010+AC:2010 “N” PN-EN ISO 8990:1998
PN-EN ISO 12567-2:2006 “N” PN-EN ISO 8990:1998
PN-EN ISO 12631:2017 PN-EN ISO 6946:2017 PN-EN ISO 10211:2017
Procedura Badawcza PB 12 wydanie 1 z 13.01.2023 r.