⚡ Instrument transformers — additional requirements for inductive voltage transformers (15 Hz to 100 Hz): measuring accuracy classes 0,1; 0,2; 0,5; 1,0; 3,0 and protective classes 3P, 6P, voltage error and phase displacement, rated outputs, rated voltages and voltage factor; PN-EN 61869-3

Electronics and EMC PN-EN 61869-3

In short

Additional requirements for new inductive voltage transformers for use with electrical measuring instruments and protective devices at frequencies from 15 Hz to 100 Hz. The test is performed according to PN-EN 61869-3:2011 (English version; implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT]); STATUS (as of 18.11.2026): PKN card: PN-EN 61869-3:2011 — English version, title “Przekładniki -- Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych”, published 27-12-2011, 32 pages, KT 81 Instrument Transformers and Low-Power Transformers, implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT], replaces PN-EN 60044-2:2001 with amendments A1:2003 and A2:2004; the card gives no withdrawal date. iTeh catalogue: IEC 61869-3:2011 — published 13.07.2011, stage PPUB (publication issued), TC 38. The procedure comprises 4 steps; it is used for: New inductive voltage transformers for measuring instruments, meters and protective devices at frequencies from 15 Hz to 100 Hz (clause 1), Checking the accuracy class: voltage error and phase displacement of measuring (Table 301) and protective 3P, 6P (Table 302) transformers, Selection of the rated output, thermal limiting output and rated voltages of the transformer (5.5, 5.301).

At a glance

  • Standard: PN-EN 61869-3:2011 (English version; implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT])
  • Category: Electronics and EMC
  • Procedure steps: 4
  • STATUS (as of 18.11.2026): PKN card: PN-EN 61869-3:2011 — English version, title “Przekładniki -- Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych”, published 27-12-2011, 32 pages, KT 81 Instrument Transformers and Low-Power Transformers, implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT], replaces PN-EN 60044-2:2001 with amendments A1:2003 and A2:2004; the card gives no withdrawal date. iTeh catalogue: IEC 61869-3:2011 — published 13.07.2011, stage PPUB (publication issued), TC 38.
  • Scope (clause 1): new inductive voltage transformers, 15 Hz to 100 Hz; read together with IEC 61869-1
  • Voltage error (3.4.3): ε = (kr × Us − Up)/Up × 100 %

Overview

WHAT THE STANDARD COVERS. According to clause 1 of IEC 61869-3:2011 this part of IEC 61869 applies to new inductive voltage transformers for use with electrical measuring instruments and electrical protective devices at frequencies from 15 Hz to 100 Hz. Requirements specific to three-phase transformers are not included, but clauses 4–10 apply to them as far as they are relevant. All transformers shall be suitable for measuring purposes, and certain types may in addition be suitable for protection; transformers for the dual purpose shall comply with all clauses of the standard.

ACCORDING TO THE TEXT OF IEC 61869-3:2011 (publisher's sample: contents, foreword, clauses 1–3 and clause 5 up to 5.301.3) and EN 61869-3:2011 (SIST sample: European foreword). The standard was prepared by IEC TC 38 (Instrument transformers); it replaces IEC 60044-2 (inductive voltage transformers). Part 3 is read together with IEC 61869-1 (general requirements, first edition of 2007) and follows its structure: a clause of Part 1 not mentioned in Part 3 applies as far as is reasonable, and additional clauses, figures and tables are numbered from 301. Definitions (clause 3): voltage transformer — an instrument transformer in which the secondary voltage, in normal conditions of use, is substantially proportional to the primary voltage and differs in phase from it by an angle which is approximately zero; unearthed and earthed voltage transformer; measuring and protective voltage transformer; residual voltage winding (in a set of three single-phase transformers connected in broken delta — to produce a residual voltage under earth-fault conditions and to damp ferro-resonance oscillations); rated voltage factor; thermal limiting output. Voltage (ratio) error in per cent: ε = (kr × Us − Up)/Up × 100 %, where kr is the rated transformation ratio, Up the actual primary voltage and Us the actual secondary voltage when Up is applied.

RATED OUTPUTS (5.5). At a power factor of 1: 1,0 – 2,5 – 5,0 – 10 VA (burden range I); at 0,8 lagging: 25 – 50 – 100 VA (burden range II); the rated output of a three-phase transformer is given per phase. Thermal limiting output: 25 – 50 – 100 VA and their decimal multiples, at rated secondary voltage and unity power factor (for a residual voltage winding referred to 8 h). Rated power-frequency withstand voltage of the earthed terminal — 3 kV (r.m.s.).

ACCURACY CLASSES (5.6). Measuring transformers: classes 0,1 – 0,2 – 0,5 – 1,0 – 3,0; the voltage error and phase displacement at rated frequency shall not exceed Table 301 at any voltage from 80 % to 120 % of rated voltage and with burdens: 0 % to 100 % of rated output at a power factor of 1 (range I) or 25 % to 100 % at 0,8 lagging (range II). Table 301: class 0,1 — ±0,1 %, ±5 minutes (±0,15 crad); 0,2 — ±0,2 %, ±10 min (±0,3 crad); 0,5 — ±0,5 %, ±20 min (±0,6 crad); 1,0 — ±1,0 %, ±40 min (±1,2 crad); 3,0 — ±3,0 %, phase displacement not specified. Errors are determined at the transformer terminals, including any fuses or resistors forming an integral part of the transformer; with tappings on the secondary winding the requirements refer to the highest ratio. Protective transformers are assigned a measuring class and class 3P or 6P (Table 302: 3P — ±3,0 %, ±120 min, ±3,5 crad; 6P — ±6,0 %, ±240 min, ±7,0 crad), checked at 5 % of rated voltage and at rated voltage multiplied by the voltage factor (1,2; 1,5 or 1,9); at 2 % of rated voltage the limits are twice as high. Residual voltage winding — class 6P or better.

RATED VOLTAGES (5.301). Primary voltage — one of the rated system voltages designated as usual values in IEC 60038 (for a single-phase transformer between line and earth — this value divided by √3). Secondary voltage: in the practice of a group of European countries 100 V and 110 V, and 200 V for extended secondary circuits; in the United States and Canada 120 V (distribution systems), 115 V (transmission systems) and 230 V (extended secondary circuits); for phase-to-earth transformers whose rated primary voltage is divided by √3 the secondary voltage is also divided by √3. Further clauses according to the table of contents — voltage factor (5.302), terminal and rating plate markings (6.13), short-circuit withstand capability (6.301), list of tests (Table 10), type tests (temperature rise, impulse voltage, EMC, accuracy, short circuit), routine tests (withstand voltage, partial discharge, accuracy) and special tests (capacitance and dielectric dissipation factor, internal arc) — the sample does not contain their text.

STATUS (as of 18.11.2026). PKN card: PN-EN 61869-3:2011 — English version, title “Przekładniki -- Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych”, published 27-12-2011, 32 pages, KT 81 Instrument Transformers and Low-Power Transformers, implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT], replaces PN-EN 60044-2:2001 with amendments A1:2003 and A2:2004; the card gives no withdrawal date. iTeh catalogue: IEC 61869-3:2011 — published 13.07.2011, stage PPUB (publication issued), TC 38. According to the European foreword EN 61869-3:2011 was approved by CENELEC on 2011-08-17 (dop 2012-05-17, dow 2014-08-17); it supersedes EN 60044-2:1999 + A1:2000 + A2:2003 and is read together with EN 61869-1:2009.

Method principle

An inductive voltage transformer reduces the primary voltage in the rated transformation ratio kr so that the secondary voltage is substantially proportional to the primary voltage and almost in phase with it. Accuracy is assessed by the voltage error ε = (kr·Us − Up)/Up × 100 % and the phase displacement Δφ, compared with the class limits at specified voltages (80–120 % for measuring classes; 5 % and the voltage factor for 3P and 6P) and burdens.

Applications

Key parameters

ParameterValue
STATUS (as of 18.11.2026)PKN card: PN-EN 61869-3:2011 — English version, title “Przekładniki -- Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych”, published 27-12-2011, 32 pages, KT 81 Instrument Transformers and Low-Power Transformers, implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT], replaces PN-EN 60044-2:2001 with amendments A1:2003 and A2:2004; the card gives no withdrawal date. iTeh catalogue: IEC 61869-3:2011 — published 13.07.2011, stage PPUB (publication issued), TC 38.
Scope (clause 1)new inductive voltage transformers, 15 Hz to 100 Hz; read together with IEC 61869-1
Voltage error (3.4.3)ε = (kr × Us − Up)/Up × 100 %
Measuring classes (Table 301)0,1: ±0,1 %, ±5 min; 0,2: ±0,2 %, ±10 min; 0,5: ±0,5 %, ±20 min; 1,0: ±1,0 %, ±40 min; 3,0: ±3,0 %, phase displacement not specified
Conditions for measuring classes (5.6.301.3)80 % to 120 % of rated voltage; range I: 0–100 % of output, cos φ = 1; range II: 25–100 % of output, cos φ = 0,8 lagging
Protective classes (Table 302)3P: ±3,0 %, ±120 min (±3,5 crad); 6P: ±6,0 %, ±240 min (±7,0 crad); at 5 % Un and Un × voltage factor (1,2; 1,5; 1,9); at 2 % Un limits ×2
Rated outputs (5.5.301)range I: 1,0 – 2,5 – 5,0 – 10 VA (cos φ = 1); range II: 25 – 50 – 100 VA (cos φ = 0,8 lagging)
Secondary voltages (5.301.2)Europe: 100 V, 110 V, 200 V; United States and Canada: 120 V, 115 V, 230 V; phase-to-earth transformers — value / √3
Earthed terminal (5.3.3.301)power-frequency withstand voltage 3 kV (r.m.s.)

Standard

Standard number
PN-EN 61869-3:2011 (English version; implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT])
Title (PL)
Przekładniki — Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych
Title (EN)
Instrument transformers — Part 3: Additional requirements for inductive voltage transformers

Step-by-step procedure

  1. Rating data

    Reading the rating plate: rated transformation ratio, primary and secondary voltages, rated output and burden range, accuracy class (measuring and possibly 3P/6P), voltage factor (5.5, 5.6, 5.301, 6.13).

  2. Error and displacement — measuring class

    At voltages from 80 % to 120 % of rated voltage and burdens of range I or II; comparison with Table 301; with two secondary windings — taking their mutual interdependence into account.

  3. Error and displacement — protective class

    At 5 % of rated voltage and at rated voltage times the voltage factor, burdens according to 5.6.302.3; comparison with Table 302 (at 2 % of rated voltage — limits twice as high).

  4. Assessment of conformity

    Voltage error and phase displacement within the class limits over the whole required range; other type, routine and special tests — according to clause 7 of the standard.

Required equipment and apparatus

EquipmentExampleIndicative price
Voltage transformer under testSingle-phase inductive measuring or protective transformer, possibly with a residual voltage winding or tappings—
Transformer burdenBurdens of range I (power factor 1) or II (0,8 lagging) from 0 % or 25 % up to 100 % of rated output (5.6.301.3)—
Set-up for measuring voltage error and phase displacementMeasurement at the transformer terminals at rated frequency (5.6.301.3); conditions of the accuracy tests — 7.2.6 and 7.3.5 of the standard—

Frequently asked questions

Which standard describes this test?

The test is performed according to PN-EN 61869-3:2011 (English version; implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT]) — “Instrument transformers — Part 3: Additional requirements for inductive voltage transformers”.

How does this method work?

An inductive voltage transformer reduces the primary voltage in the rated transformation ratio kr so that the secondary voltage is substantially proportional to the primary voltage and almost in phase with it. Accuracy is assessed by the voltage error ε = (kr·Us − Up)/Up × 100 % and the phase displacement Δφ, compared with the class limits at specified voltages (80–120 % for measuring classes; 5 % and the voltage factor for 3P and 6P) and burdens.

What is the measuring range and accuracy?

STATUS (as of 18.11.2026): PKN card: PN-EN 61869-3:2011 — English version, title “Przekładniki -- Część 3: Wymagania szczegółowe dotyczące przekładników napięciowych indukcyjnych”, published 27-12-2011, 32 pages, KT 81 Instrument Transformers and Low-Power Transformers, implements EN 61869-3:2011 and IEC 61869-3:2011 [IDT], replaces PN-EN 60044-2:2001 with amendments A1:2003 and A2:2004; the card gives no withdrawal date. iTeh catalogue: IEC 61869-3:2011 — published 13.07.2011, stage PPUB (publication issued), TC 38.; Scope (clause 1): new inductive voltage transformers, 15 Hz to 100 Hz; read together with IEC 61869-1; Voltage error (3.4.3): ε = (kr × Us − Up)/Up × 100 %; Measuring classes (Table 301): 0,1: ±0,1 %, ±5 min; 0,2: ±0,2 %, ±10 min; 0,5: ±0,5 %, ±20 min; 1,0: ±1,0 %, ±40 min; 3,0: ±3,0 %, phase displacement not specified.

How long does the test take?

The procedure comprises 4 steps. The standard does not give a duration for every stage — the laboratory's own procedure decides.

What equipment is required?

Voltage transformer under test, Transformer burden, Set-up for measuring voltage error and phase displacement.

Where is this test used?

New inductive voltage transformers for measuring instruments, meters and protective devices at frequencies from 15 Hz to 100 Hz (clause 1); Checking the accuracy class: voltage error and phase displacement of measuring (Table 301) and protective 3P, 6P (Table 302) transformers; Selection of the rated output, thermal limiting output and rated voltages of the transformer (5.5, 5.301); Residual voltage windings in broken delta — detection of earth faults and damping of ferro-resonance (3.1.308, 5.6.302.4).