⚡ Immunity of electrical and electronic equipment to damped oscillatory waves — slow (100 kHz and 1 MHz, HV/MV substations) and fast (3, 10 and 30 MHz, gas insulated substations, HEMP) on power, signal, control and earth ports; PN-EN IEC 61000-4-18
In short
Basic EMC publication describing the immunity test of electrical and electronic equipment under operational conditions to repetitive damped oscillatory waves: slow ones (100 kHz and 1 MHz) occurring mainly in cables in high and medium voltage substations, and fast ones (above 1 MHz; standard 3, 10 and 30 MHz) in gas insulated substations, in some cases air insulated substations, or due to the high-altitude electromagnetic pulse (HEMP). The test is performed according to PN-EN IEC 61000-4-18:2019-08 (English version, published 06-08-2019; implements EN IEC 61000-4-18:2019 and IEC 61000-4-18:2019 [IDT]) with corrigendum PN-EN IEC 61000-4-18:2019-08/AC:2019-12; STATUS (as of 27.11.2026): PKN card: PN-EN IEC 61000-4-18:2019-08 — English version (06-08-2019, 66 pages), KT 104, implements EN IEC 61000-4-18:2019 [IDT] and IEC 61000-4-18:2019 [IDT], replaces PN-EN 61000-4-18:2009 and PN-EN 61000-4-18:2009/A1:2011; additional element: corrigendum AC:2019-12E; the card gives no withdrawal date. The procedure comprises 4 steps; it is used for: Equipment installed in high and medium voltage substations — slow wave 100 kHz and 1 MHz (Clause 1, 4.2), Equipment in gas insulated substations (GIS), in some cases air insulated substations (AIS) — fast wave (Clause 1), Equipment required to be immune to the HEMP electromagnetic pulse (Clause 1).
At a glance
- Standard: PN-EN IEC 61000-4-18:2019-08 (English version, published 06-08-2019; implements EN IEC 61000-4-18:2019 and IEC 61000-4-18:2019 [IDT]) with corrigendum PN-EN IEC 61000-4-18:2019-08/AC:2019-12
- Category: Electronics and EMC
- Procedure steps: 4
- STATUS (as of 27.11.2026): PKN card: PN-EN IEC 61000-4-18:2019-08 — English version (06-08-2019, 66 pages), KT 104, implements EN IEC 61000-4-18:2019 [IDT] and IEC 61000-4-18:2019 [IDT], replaces PN-EN 61000-4-18:2009 and PN-EN 61000-4-18:2009/A1:2011; additional element: corrigendum AC:2019-12E; the card gives no withdrawal date.
- Slow wave (4.1, 4.2): from 100 kHz to 1 MHz; standard 100 kHz and 1 MHz; repetition rates 40/s and 400/s
- Fast wave (4.1, Table 1): above 1 MHz; standard 3, 10 and 30 MHz
Overview
WHAT THE STANDARD COVERS. According to Clause 1 of IEC 61000-4-18:2019 the standard focuses on the immunity requirements and test methods for electrical and electronic equipment, under operational conditions, with regard to: a) repetitive slow damped oscillatory waves occurring mainly in power, control and signal cables installed in high voltage and medium voltage (HV/MV) substations; b) repetitive fast damped oscillatory waves occurring mainly in cables in gas insulated substations (GIS), in some cases also air insulated substations (AIS), or in any installation due to HEMP. Its object is a common and reproducible reference for evaluating immunity with waves applied to supply, signal, control and earth ports. It defines test voltage and current waveforms, ranges of test levels, test equipment, calibration and verification procedures of the test equipment, test setups and the test procedure. It is a basic EMC publication according to IEC Guide 107.
ACCORDING TO THE TEXT OF IEC 61000-4-18:2019 (second edition; the publisher's sample covers the contents, foreword, introduction and Clauses 1–4.2; the corrigendum of August 2019 is included in the copy). The standard was prepared by subcommittee IEC SC 77B of IEC TC 77. The second edition replaces the first edition of 2006 and its Amendment 1:2010; changes according to the foreword: mathematical modelling of the waveform, new Annex B (measurement uncertainty), a high-speed CDN, calibration procedures for CDNs, the capacitive coupling clamp on interconnection lines for fast waves, a test procedure for DC/DC converters when the CDN does not work, and new Annex C on powering EUTs having DC/DC converters at the input.
TYPES OF WAVES (4.1, Table 1). The slow damped oscillatory wave covers oscillation frequencies from 100 kHz to 1 MHz, the fast one — above 1 MHz. The ideal waveform formula w(t) has for the open circuit voltage the parameters: fast 30 MHz — K = 1.19, n = 1.67, t1 = 2.26 ns, t2 = 126 ns, φ = −π/2; fast 10 MHz — K = 1.04, n = 2.65, t1 = 1.69 ns, t2 = 377 ns, φ = −π/4; fast 3 MHz — K = 1.07, n = 2.30, t1 = 2.89 ns, t2 = 1.26 µs, φ = 0; slow 1 MHz — K = 1.12, n = 2.45, t1 = 49.8 ns, t2 = 3.77 µs, φ = −π/4; slow 100 kHz — K = 1.04, n = 1.96, t1 = 32.7 ns, t2 = 37.7 µs, φ = 0 (in each case A = Pk1).
SLOW WAVE (4.2). It is representative of the switching of disconnectors in HV/MV open-air substations, particularly of HV busbars; opening and closing of HV disconnectors gives transients with rise times of the order of some tens of nanoseconds. The oscillation frequency depends on the circuit length and propagation time — from about 100 kHz to a few MHz (busbars from some tens to hundreds of metres, even 400 m); 1 MHz is considered representative of most situations and 100 kHz appropriate for large HV substations. The repetition frequency varies from a few hertz to a few kilohertz; repetition rates of 40/s and 400/s are a compromise between the duration of the phenomena, the frequencies and the energy applied to the circuits under test.
WHAT WE DO NOT GIVE HERE. The sample ends at 4.2 — we do not reproduce the description of the fast wave (4.3), the test levels (Tables 2 and 3), generators, CDNs, clamps, calibration, setups or the test procedure. Corrigendum AC:2019-12 (IEC 61000-4-18:2019/COR1:2019, text read) replaces Formula (B.1) and the formula in the second paragraph of B.4.5 (rise time of the step response and bandwidth of the measuring system) — it concerns only Annex B on measurement uncertainty.
STATUS (as of 27.11.2026). PKN card: PN-EN IEC 61000-4-18:2019-08 "Kompatybilność elektromagnetyczna (EMC) -- Część 4-18: Metody badań i pomiarów -- Badanie odporności na tłumiony przebieg oscylacyjny" — English version (published 06-08-2019, 66 pages), KT 104 (electromagnetic compatibility), implements EN IEC 61000-4-18:2019 [IDT] and IEC 61000-4-18:2019 [IDT], replaces PN-EN 61000-4-18:2009 (Polish version) and PN-EN 61000-4-18:2009/A1:2011 (English version), ICS 33.100.20; additional element PN-EN IEC 61000-4-18:2019-08/AC:2019-12E (corrigendum approved by the President of PKN on 3 December 2019, implementing EN IEC 61000-4-18:2019/AC:2019-10 and IEC 61000-4-18:2019/AC1:2019); the card gives no withdrawal date.
Method principle
A repetitive damped oscillatory wave — slow (100 kHz or 1 MHz) or fast (3, 10 or 30 MHz), shaped according to the w(t) formula with the parameters of Table 1 — is applied to the power, signal, control and earth ports of the equipment under test, and its operation is observed; the type of wave corresponds to the environment: HV/MV open-air substations or gas insulated substations and HEMP.
Applications
- Equipment installed in high and medium voltage substations — slow wave 100 kHz and 1 MHz (Clause 1, 4.2)
- Equipment in gas insulated substations (GIS), in some cases air insulated substations (AIS) — fast wave (Clause 1)
- Equipment required to be immune to the HEMP electromagnetic pulse (Clause 1)
- Immunity tests required by product standards that refer to IEC 61000-4-18 (IEC Guide 107)
Key parameters
| Parameter | Value |
|---|---|
| STATUS (as of 27.11.2026) | PKN card: PN-EN IEC 61000-4-18:2019-08 — English version (06-08-2019, 66 pages), KT 104, implements EN IEC 61000-4-18:2019 [IDT] and IEC 61000-4-18:2019 [IDT], replaces PN-EN 61000-4-18:2009 and PN-EN 61000-4-18:2009/A1:2011; additional element: corrigendum AC:2019-12E; the card gives no withdrawal date. |
| Slow wave (4.1, 4.2) | from 100 kHz to 1 MHz; standard 100 kHz and 1 MHz; repetition rates 40/s and 400/s |
| Fast wave (4.1, Table 1) | above 1 MHz; standard 3, 10 and 30 MHz |
| w(t) parameters — slow 1 MHz / 100 kHz (Table 1) | K = 1.12 / 1.04; n = 2.45 / 1.96; t1 = 49.8 ns / 32.7 ns; t2 = 3.77 µs / 37.7 µs; φ = −π/4 / 0 |
| w(t) parameters — fast 3 / 10 / 30 MHz (Table 1) | K = 1.07 / 1.04 / 1.19; n = 2.30 / 2.65 / 1.67; t1 = 2.89 / 1.69 / 2.26 ns; t2 = 1.26 µs / 377 ns / 126 ns; φ = 0 / −π/4 / −π/2 |
| Ports (Clause 1) | supply, signal, control and earth |
| Corrigendum AC:2019-12 (COR1:2019) | new Formula (B.1) and formula in the second paragraph of B.4.5 — Annex B on measurement uncertainty |
Standard
- Standard number
- PN-EN IEC 61000-4-18:2019-08 (English version, published 06-08-2019; implements EN IEC 61000-4-18:2019 and IEC 61000-4-18:2019 [IDT]) with corrigendum PN-EN IEC 61000-4-18:2019-08/AC:2019-12
- Title (PL)
- Kompatybilność elektromagnetyczna (EMC) — Część 4-18: Metody badań i pomiarów — Badanie odporności na tłumiony przebieg oscylacyjny
- Title (EN)
- Electromagnetic compatibility (EMC) — Part 4-18: Testing and measurement techniques — Damped oscillatory wave immunity test
Step-by-step procedure
-
Choice of waveform
Slow wave (100 kHz, 1 MHz) for the HV/MV substation environment, fast wave (3, 10, 30 MHz) for gas insulated substations and HEMP; level from the product standard (Clause 5, Tables 2 and 3).
-
Preparation of equipment
Generator, CDNs or capacitive clamps; calibration and verification according to Clause 6 and 7.2.
-
Test
Application of the wave to the supply, signal, control and earth ports in the setup of Clause 7 and with the procedure of Clause 8.
-
Evaluation and report
Evaluation of the operation of the equipment according to the criteria of the product standard (Clauses 9 and 10).
Required equipment and apparatus
| Equipment | Example | Indicative price |
|---|---|---|
| Slow damped oscillatory wave generator (SDOWG) and fast damped oscillatory wave generator (FDOWG) (6.2) | According to the contents: 6.2.1 and 6.2.2 | — |
| Coupling/decoupling networks (CDN) and capacitive coupling clamps (6.3–6.5) | Capacitive clamps — for interconnection lines with the fast wave; calibration of CDNs and clamps (6.4, 6.5.2) | — |
Frequently asked questions
Which standard describes this test?
The test is performed according to PN-EN IEC 61000-4-18:2019-08 (English version, published 06-08-2019; implements EN IEC 61000-4-18:2019 and IEC 61000-4-18:2019 [IDT]) with corrigendum PN-EN IEC 61000-4-18:2019-08/AC:2019-12 — “Electromagnetic compatibility (EMC) — Part 4-18: Testing and measurement techniques — Damped oscillatory wave immunity test”.
How does this method work?
A repetitive damped oscillatory wave — slow (100 kHz or 1 MHz) or fast (3, 10 or 30 MHz), shaped according to the w(t) formula with the parameters of Table 1 — is applied to the power, signal, control and earth ports of the equipment under test, and its operation is observed; the type of wave corresponds to the environment: HV/MV open-air substations or gas insulated substations and HEMP.
What is the measuring range and accuracy?
STATUS (as of 27.11.2026): PKN card: PN-EN IEC 61000-4-18:2019-08 — English version (06-08-2019, 66 pages), KT 104, implements EN IEC 61000-4-18:2019 [IDT] and IEC 61000-4-18:2019 [IDT], replaces PN-EN 61000-4-18:2009 and PN-EN 61000-4-18:2009/A1:2011; additional element: corrigendum AC:2019-12E; the card gives no withdrawal date.; Slow wave (4.1, 4.2): from 100 kHz to 1 MHz; standard 100 kHz and 1 MHz; repetition rates 40/s and 400/s; Fast wave (4.1, Table 1): above 1 MHz; standard 3, 10 and 30 MHz; w(t) parameters — slow 1 MHz / 100 kHz (Table 1): K = 1.12 / 1.04; n = 2.45 / 1.96; t1 = 49.8 ns / 32.7 ns; t2 = 3.77 µs / 37.7 µs; φ = −π/4 / 0.
How long does the test take?
The procedure comprises 4 steps. The standard does not give a duration for every stage — the laboratory's own procedure decides.
What equipment is required?
Slow damped oscillatory wave generator (SDOWG) and fast damped oscillatory wave generator (FDOWG) (6.2), Coupling/decoupling networks (CDN) and capacitive coupling clamps (6.3–6.5).
Where is this test used?
Equipment installed in high and medium voltage substations — slow wave 100 kHz and 1 MHz (Clause 1, 4.2); Equipment in gas insulated substations (GIS), in some cases air insulated substations (AIS) — fast wave (Clause 1); Equipment required to be immune to the HEMP electromagnetic pulse (Clause 1); Immunity tests required by product standards that refer to IEC 61000-4-18 (IEC Guide 107).
Which laboratory can perform this test?
The test is performed by laboratories accredited to ISO/IEC 17025. On LabCoda you can find them by the standard number PN-EN IEC 61000-4-18.