🔥 Non-combustibility test of products — specimen in a tube furnace, temperature rise, mass loss and duration of sustained flaming; homogeneous products and substantial components of non-homogeneous products; PN-EN ISO 1182:2020-12
In short
A test from the reaction to fire group, intended for identifying construction products that are not entirely inert but at a temperature of about 750 °C release very little heat and flame: the specimen is inserted into a vertical tube furnace and the temperature rise, the mass loss and sustained flaming (at least 5 s) are assessed. The test is performed according to PN-EN ISO 1182:2020-12 (English version; adopts EN ISO 1182:2020 [IDT] and ISO 1182:2020 [IDT]); Scope of application (1 and introduction): homogeneous products and substantial components of non-homogeneous products; whole non-homogeneous products are NOT tested by this standard. The procedure comprises 6 steps; it is used for: Construction products in reaction to fire tests — non-combustibility, Insulating materials, masonry units, renders, mortars, adhesives and fibre-cement products — homogeneous products and substantial components of non-homogeneous products, Materials in shipbuilding — together with the International Code for Application of Fire Test Procedures, part 1.
At a glance
- Standard: PN-EN ISO 1182:2020-12 (English version; adopts EN ISO 1182:2020 [IDT] and ISO 1182:2020 [IDT])
- Category: Construction
- Procedure steps: 6
- Scope of application (1 and introduction): homogeneous products and substantial components of non-homogeneous products; whole non-homogeneous products are NOT tested by this standard
- Furnace tube (4.2.1): alumina material (Al2O3 > 89 %), density (2800 ± 300) kg/m³, height (150 ± 1) mm, internal diameter (75 ± 1) mm, wall (10 ± 1) mm
- Furnace thermocouples (4.4): type K or N, class 1, wire 0.3 mm, sheath 1.5 mm; TC1 and TC2 (10 ± 0.5) mm from the wall; initial calibration at 750 °C; replacement after 200 tests
Overview
STATUS (as of 16.11.2026). PN-EN ISO 1182:2020-12 — English version, published 07-12-2020, 44 pages, KT 180 Fire Safety of Buildings, “Adopts: EN ISO 1182:2020 [IDT], ISO 1182:2020 [IDT]”, “Replaces: PN-EN ISO 1182:2010 – Polish version, PN-EN ISO 1182:2010 – English version”; the PKN card has no withdrawal note. The Polish version PN-EN ISO 1182:2010 (published 14-01-2013) has been withdrawn since 07-12-2020 — the current edition exists only in English. ISO last reviewed and confirmed ISO 1182:2020 (sixth edition, 2020-06) on 16.10.2025 (ISO standard page: stage 90.93). The description below follows the text of ISO 1182:2020.
WHAT THE STANDARD COVERS. Scope from the PKN card of PN-EN ISO 1182:2020-12, in full (our translation): "This document specifies a test method for assessing the non-combustibility, under specified conditions, of homogeneous products and of substantial components of non-homogeneous products. Information on the precision of the test method is given in Annex A" (no full stop on the card). We read the content of the method in the sample extract of ISO 1182:2020 from the cover to clause 4.6 (contact thermocouple), with the table of contents; we do not have clauses 5–9 or the annexes.
ACCORDING TO THE TEXT OF ISO 1182:2020 (foreword, introduction, clauses 1–4). The standard was prepared by ISO/TC 92 "Fire safety", subcommittee SC 1 "Fire initiation and growth", together with CEN/TC 127 "Fire safety in buildings" (Vienna Agreement); the sixth edition (2020-06) replaced the fifth (ISO 1182:2010). Main changes according to the foreword: a second furnace thermocouple (clauses 4.4, 7.2.2, 7.2.4, 8.3, clause 9, Figure 2), a changed procedure for calibrating the furnace wall temperature, formulae (16) and (17) aligned with Table 3, a smaller permissible spread of specimen dimensions (clause 5) and a corrected Annex D. Introduction: the test serves to identify construction products which are not entirely inert but, exposed to a temperature of about 750 °C, release only a very limited amount of heat and flame; the standard was restricted to homogeneous products and substantial components of non-homogeneous products, because the construction of a specimen of a non-homogeneous product strongly influences the result — non-homogeneous products cannot be tested according to this standard. References (2): ISO 13943 (fire safety vocabulary), IEC 60584-1 (thermocouples) and EN 13238 (conditioning and selection of substrates in reaction to fire tests of construction products). Definitions (3): material — a single substance or a uniformly dispersed mixture (examples in the standard: metal, stone, timber, concrete, mineral wool with a uniformly dispersed binder, polymers); loose-fill material — without a defined shape; homogeneous product — consisting of one material of uniform density and composition; substantial component — a layer with a mass per unit area of at least 1.0 kg/m² or a thickness of at least 1.0 mm, non-substantial — below 1.0 kg/m² and below 1.0 mm; sustained flaming — a flame persisting on any visible part of the specimen for 5 s or longer; steady, blue, luminous zones of gas are not regarded as flame and are only noted in the observations. Apparatus (4): a furnace of a refractory tube surrounded by a heating coil in an insulated housing, with a cone-shaped air-flow stabilizer at the bottom and a draught shield at the top, on a stand, with a specimen holder and an insertion device; thermocouples for measuring the furnace and wall temperatures and a temperature sensor on the furnace axis; additional thermocouples for the surface and centre temperature of the specimen are described in Annex C (their use is optional). Furnace tube of refractory alumina material: Al2O3 over 89 %, SiO2 + Al2O3 over 98 %, Fe2O3 below 0.45 %, TiO2 below 0.25 %, Mn3O4 below 0.1 %; density (2800 ± 300) kg/m³, height (150 ± 1) mm, internal diameter (75 ± 1) mm, wall (10 ± 1) mm; insulating housing 150 mm high with a 10 mm wall. Stabilizer: length 500 mm, tapering from (75 ± 1) mm to (10 ± 0.5) mm, 1 mm steel sheet, tight and smooth joint with the furnace, upper half insulated; draught shield 50 mm high, internal diameter (75 ± 1) mm; draught screen at the stand 550 mm high, the bottom of the cone 250 mm above the base. Specimen holder of nickel-chromium wire or heat-resistant steel, with a fine mesh tray at the bottom, mass (15 ± 2) g — with ageing the holder loses mass, which must be checked regularly; suspended on a stainless steel tube with an external diameter of 6 mm; the insertion device places the geometric centre of the specimen at the geometric centre of the furnace; holder for loose-fill materials — cylindrical, of mesh, open at the top, mass at most 30 g. Thermocouples: type K or N, tolerance class 1 according to IEC 60584-1, wire 0.3 mm, external diameter 1.5 mm, insulated and ungrounded junction, sheath of stainless steel or nickel alloy; new thermocouples are artificially aged before use (e.g. an hour of furnace operation without a specimen); the two furnace thermocouples, TC1 and TC2, have their junctions (10 ± 0.5) mm from the tube wall at the height of its geometric centre, protrude (40 ± 5) mm beyond the guide, are initially calibrated at 750 °C (the correction is added to the readings) and are replaced after 200 tests. Axial sensor — a thermocouple soldered into the centre of a copper cylinder with a diameter of (10 ± 0.2) mm and a height of (15 ± 0.2) mm; contact thermocouple bent according to Figure 4.
WHERE A SEEMINGLY CORRECT RESULT IS EASY TO GET. First — non-homogeneous product: the standard tests only homogeneous products and substantial components of non-homogeneous products; according to the introduction a whole non-homogeneous product cannot be tested by it, because the construction of the specimen strongly influences the result. Second — flame: sustained flaming is a flame lasting at least 5 s; steady blue luminous zones of gas are not flame and go only into the observations. Third — thermocouples: the 2020 edition introduced the second furnace thermocouple and changed the calibration of the wall temperature; thermocouples are replaced after 200 tests, and new ones must be aged — a result from an improperly prepared measuring chain looks the same as a correct one. Fourth — the specimen holder loses mass with ageing, and its mass is to be (15 ± 2) g. Fifth — the edition: a reference to “ISO 1182” without a year means the 2020 edition with the second furnace thermocouple today; a Polish version existed only for the withdrawn 2010 edition. Sixth — test versus classification: the standard describes a test method; the criteria by which a product is assigned to a reaction to fire class are not in the extract read and we do not give them here.
WHAT WE DO NOT GIVE HERE. We do not have clauses 5–9 or the annexes: the dimensions and preparation of the specimens, their number, conditioning, the test environment, the setting up and stabilization of the furnace (including the operating temperature of the furnace and the stability criteria), the calibration of the wall and furnace temperature, the test procedure and observations, the formulae for mass loss and temperature rise, the content of the report, the precision and example furnace designs.
Method principle
A specimen of a homogeneous product or of a substantial component of a non-homogeneous product is inserted into a vertical tube furnace of a refractory alumina tube, heated by an electric coil, so that its geometric centre is at the geometric centre of the furnace; the furnace temperature is measured by two thermocouples near the wall, and additional thermocouples may measure the surface and centre temperature of the specimen. The result describes the mass loss, sustained flaming (at least 5 s) and the temperature rise (ISO 1182:2020, clauses 1–4 and table of contents). According to the introduction the test identifies products which at a temperature of about 750 °C release very little heat and flame.
Applications
- Construction products in reaction to fire tests — non-combustibility
- Insulating materials, masonry units, renders, mortars, adhesives and fibre-cement products — homogeneous products and substantial components of non-homogeneous products
- Materials in shipbuilding — together with the International Code for Application of Fire Test Procedures, part 1
Key parameters
| Parameter | Value |
|---|---|
| Scope of application (1 and introduction) | homogeneous products and substantial components of non-homogeneous products; whole non-homogeneous products are NOT tested by this standard |
| Furnace tube (4.2.1) | alumina material (Al2O3 > 89 %), density (2800 ± 300) kg/m³, height (150 ± 1) mm, internal diameter (75 ± 1) mm, wall (10 ± 1) mm |
| Furnace thermocouples (4.4) | type K or N, class 1, wire 0.3 mm, sheath 1.5 mm; TC1 and TC2 (10 ± 0.5) mm from the wall; initial calibration at 750 °C; replacement after 200 tests |
| Sustained flaming (3.8) | a flame on a visible part of the specimen lasting at least 5 s; blue luminous zones of gas are not flame |
| Substantial component (3.6) | a layer with a mass per unit area of at least 1.0 kg/m² or a thickness of at least 1.0 mm |
Standard
- Standard number
- PN-EN ISO 1182:2020-12 (English version; adopts EN ISO 1182:2020 [IDT] and ISO 1182:2020 [IDT])
- Title (PL)
- Badania reakcji na ogień wyrobów — Badanie niepalności
- Title (EN)
- Reaction to fire tests for products — Non-combustibility test
Step-by-step procedure
-
Qualifying the product
Establish whether the product is homogeneous; in a non-homogeneous product test only the substantial components (at least 1.0 kg/m² or 1.0 mm) — a whole non-homogeneous product is not tested by this standard (introduction, 3.4–3.7).
-
Preparing the apparatus
Check the mass of the specimen holder ((15 ± 2) g), the position of the furnace thermocouples ((10 ± 0.5) mm from the wall, (40 ± 5) mm beyond the guide) and their condition (replacement after 200 tests, new ones aged) (4.3–4.4).
-
Specimens, conditioning, stabilization and calibration
Clauses 5–7.3, which we do not have — WE DO NOT GIVE the dimensions of the specimens, the conditioning, the furnace stabilization conditions and the calibration.
-
Test
Insert the specimen so that its centre is at the geometric centre of the furnace, and observe the flame — sustained flaming is a flame lasting at least 5 s (3.8, 4.3.2); WE DO NOT GIVE the procedure of clause 7.4.
-
Results
Mass loss, flaming and temperature rise according to clause 8 — WE DO NOT GIVE the formulae.
-
Report
State the edition of the standard; WE DO NOT GIVE the content of the report from clause 9.
Required equipment and apparatus
| Equipment | Example | Indicative price |
|---|---|---|
| Tube furnace | Tube of refractory alumina material (150 ± 1) mm × internal Ø (75 ± 1) mm, wall (10 ± 1) mm, heating coil in an insulated housing of 150 mm (ISO 1182:2020, 4.2.1) | — |
| Air-flow stabilizer and shields | Cone 500 mm of 1 mm steel sheet, tapering from 75 mm to 10 mm; draught shield 50 mm; screen 550 mm, bottom of the cone 250 mm above the base (4.2.1–4.2.3) | — |
| Specimen holder and insertion device | NiCr wire or heat-resistant steel with a mesh tray, mass (15 ± 2) g; for loose-fill materials a mesh cylinder of up to 30 g; centre of the specimen at the geometric centre of the furnace (4.3) | — |
| Furnace thermocouples TC1 and TC2 | Type K or N, class 1 according to IEC 60584-1, wire 0.3 mm, sheath 1.5 mm; aged before use; replacement after 200 tests (4.4) | — |
| Axial sensor and contact thermocouple | Thermocouple in a copper cylinder Ø (10 ± 0.2) mm × (15 ± 0.2) mm; contact thermocouple bent according to Figure 4 (4.5–4.6) | — |
| Additional thermocouples (optional) | For the surface and centre temperature of the specimen — according to Annex C, which we do not have | — |
Health and safety (OHS)
- Work at a furnace heated to a temperature of the order of 750 °C (introduction, calibration of thermocouples at 750 °C) — protection against burns, in accordance with the instructions for the test rig
Frequently asked questions
Which standard describes this test?
The test is performed according to PN-EN ISO 1182:2020-12 (English version; adopts EN ISO 1182:2020 [IDT] and ISO 1182:2020 [IDT]) — “Reaction to fire tests for products — Non-combustibility test”.
How does this method work?
A specimen of a homogeneous product or of a substantial component of a non-homogeneous product is inserted into a vertical tube furnace of a refractory alumina tube, heated by an electric coil, so that its geometric centre is at the geometric centre of the furnace; the furnace temperature is measured by two thermocouples near the wall, and additional thermocouples may measure the surface and centre temperature of the specimen. The result describes the mass loss, sustained flaming (at least 5 s) and the temperature rise (ISO 1182:2020, clauses 1–4 and table of contents).
What is the measuring range and accuracy?
Scope of application (1 and introduction): homogeneous products and substantial components of non-homogeneous products; whole non-homogeneous products are NOT tested by this standard; Furnace tube (4.2.1): alumina material (Al2O3 > 89 %), density (2800 ± 300) kg/m³, height (150 ± 1) mm, internal diameter (75 ± 1) mm, wall (10 ± 1) mm; Furnace thermocouples (4.4): type K or N, class 1, wire 0.3 mm, sheath 1.5 mm; TC1 and TC2 (10 ± 0.5) mm from the wall; initial calibration at 750 °C; replacement after 200 tests; Sustained flaming (3.8): a flame on a visible part of the specimen lasting at least 5 s; blue luminous zones of gas are not flame.
How long does the test take?
The procedure comprises 6 steps. The standard does not give a duration for every stage — the laboratory's own procedure decides.
What equipment is required?
Tube furnace, Air-flow stabilizer and shields, Specimen holder and insertion device, Furnace thermocouples TC1 and TC2, Axial sensor and contact thermocouple, Additional thermocouples (optional).
Where is this test used?
Construction products in reaction to fire tests — non-combustibility; Insulating materials, masonry units, renders, mortars, adhesives and fibre-cement products — homogeneous products and substantial components of non-homogeneous products; Materials in shipbuilding — together with the International Code for Application of Fire Test Procedures, part 1.
What safety precautions apply?
Work at a furnace heated to a temperature of the order of 750 °C (introduction, calibration of thermocouples at 750 °C) — protection against burns, in accordance with the instructions for the test rig.
Which laboratory can perform this test?
The test is performed by laboratories accredited to ISO/IEC 17025. On LabCoda you can find them by the standard number PN-EN ISO 1182.